浙大中控DCS卡件日常维护时需要对哪些数据进行备份?

2021-01-18 18:28:52 来源:http://www.sdjkyqyb.com/ 53

浙大中控DCS卡件日常维护时需要对哪些数据进行备份?
What data should be backed up during daily maintenance of DCS card in Zhejiang University?
需要对组态、PID参数、工艺参数(设定值)、系统安装软件、电脑驱动以及认为重要的趋势、报表等数据进行备份。
It is necessary to back up the configuration, PID parameters, process parameters (set values), system installation software, computer drivers, trends and reports that are considered important.
回路无输出问题的处理?
How to deal with the problem of no output in the loop?
某项目使用中控JX-300X系统。用户自行增加一单回路后,无输出。投自动时会自动跳回手动状态。经检查程序,发现用户增加的自定义回路,回路编号为09;而BSC模块中,模拟量输出对应的模块为08。而08自定义回路组态后前期并未实际应用。因此用户在回路程序段中发现前期使用的回路号为07,便自行将08回路号将在本次增加的BSC模块内。因此,在组态下载后,回路与实际输出并未一一对应,因此发生本次故障。将程序中BCS模块的回路编号更改为09,编译下载后正常。
A project uses central control JX-300X system. After the user adds a single circuit, there is no output. It will automatically jump back to the manual state when it is automatic. After checking the program, it is found that the user-defined circuit number is 09, while the module corresponding to analog output in BSC module is 08. However, 08 custom loop configuration has not been applied in practice. Therefore, if the user finds that the previously used loop number is 07 in the loop program section, he will put the 08 loop number in the BSC module added this time. Therefore, after the configuration download, the circuit and the actual output did not correspond one by one, so this fault occurred. The circuit number of BCS module in the program is changed to 09, which is normal after compiling and downloading.
主控卡故障排除案例:
Troubleshooting case of main control card:
故障现象:某JX-300X DCS卡件系统检修后发现两块主控卡都不工作,主控卡所有的指示灯都不亮。
Fault phenomenon: after maintenance of a JX-300X DCS card system, it is found that two main control cards are not working, and all indicator lights of the main control card are not on.
             浙大中控DCS卡件
故障排除:
Troubleshooting:
1.将两块主控卡依次重新插在相邻控制站主控卡位置,主控卡指示灯正常显示,排除主控卡本身硬件故障。
1. Insert the two main control cards into the main control cards of the adjacent control station in turn, and the indicator light of the main control card will display normally, so as to eliminate the hardware fault of the main control card.
2.将一块IO卡件插在原主控卡槽位,IO卡件指示灯显示正常,基本将故障点定在主控卡槽位上。3.万用表测量各机笼后5V、24V电压:主控卡机
2. Insert an IO card into the original master card slot, the indicator light of IO card is normal, and the fault point is basically located in the master card slot. 3. Measure the 5V and 24V voltage behind each cage with a multimeter: main control card
笼和二个机笼24V为0;测量电源箱后电源5V、24V供电都正常,而24V输出到机笼的接线断开,重新接上24V电源线后,主控卡正常工作,故障消除。
The 24 V of the cage and the two cages is 0; after measuring the power supply box, the power supply of 5 V and 24 V is normal, and the wiring of 24 V output to the cage is disconnected. After re connecting the 24 V power line, the main control card works normally and the fault is eliminated.
以上是"浙大中控DCS卡件日常维护时需要对哪些数据进行备份"介绍,希望对大家有所帮助,如想了解更多精彩资讯请点击我们的网站:http://www.sdjkyqyb.com
The above is the introduction of "what data need to be backed up during daily maintenance of DCS card of Zhejiang University central control". I hope it can help you. For more wonderful information, please click our website: http://www.sdjkyqyb.com  .