大修后DCS系统上电以及接地检查问题

2022-07-29 11:49:04 来源:http://www.sdjkyqyb.com/ 53

在DCS控制系统安装之前需要重视工程设计及施工阶段的工作,在DCS投运后对这些进行改造比较困难,因此出现问题后改造远不如出现问题之前做好相应的措施。下面来讲讲大修后DCS系统上电以及接地检查问题。
Before the installation of DCS control system, we need to pay attention to the work of engineering design and construction stage. It is difficult to transform these after DCS is put into operation. Therefore, the transformation after problems occur is far better than the corresponding measures before problems occur. Let's talk about the power on and grounding inspection of DCS system after overhaul.
大修后DCS系统如何上电,如何对DCS供电检查?
How to power on DCS system after overhaul and how to check DCS power supply?
DCS系统对供电质量有一定要求,大修后DCS上电应注意:
DCS system has certain requirements for power supply quality, and attention shall be paid to DCS power on after overhaul:
1、确认外部供电是否平稳,如检修期间电压不稳不要上电。
1. Confirm whether the external power supply is stable. If the voltage is unstable during maintenance, do not power on.
2、测试外部供电电压是否符合198V-242V要求。
2. Test whether the external power supply voltage meets the requirements of 198v-242v.
3、上电时按先总电源,再操作站,控制柜,外配柜顺序上电(断电则相反)。
3. When powered on, power on in the order of main power supply first, then operation station, control cabinet and external distribution cabinet (the reverse is true when powered off).
4、上电后对浙大中控dcs卡件XP313故障报警、电压故障报警、交换机和网络检查,对供电电压测试。
4. After power on, check the xp313 fault alarm, voltage fault alarm, switch and network of Zhejiang University central control DCS card, and test the power supply voltage.
5、用万用表可检查DCS每个机笼的5V、24V电压,如低于5V、24V则不正常。如需对供电质量深入检查,需用示波器或电能质量分析仪检测分析。
5. Use a multimeter to check the 5V and 24V voltage of each cage of DCS. If it is lower than 5V and 24V, it is abnormal. If in-depth inspection of power supply quality is required, oscilloscope or power quality analyzer shall be used for detection and analysis.
专家建议:系统维护负责人确认条件具备方可上电。应严格遵照上电步骤进行。
Expert suggestion: the person in charge of system maintenance can power on only after confirming that the conditions are met. Strictly follow the power on steps.
浙大中控dcs卡件XP313
如何简单检查DCS系统接地?
How to simply check DCS system grounding?
A:DCS接地是一个很复杂的问题,涉及到接地地点,接地方式,接地电阻大小等从现场到DCS机柜的诸多节点和环节。但日常对DCS的常规检查主要有几个方面:
A: DCS grounding is a very complex problem, involving many nodes and links from the site to DCS cabinet, such as grounding point, grounding mode, grounding resistance, etc. However, the routine inspection of DCS mainly includes several aspects:
1、DCS机柜应采用单点接地方式,检查是否有可能导致多点接地的地方出现,比如机柜与槽钢的接触,接地点是否为单条引下线(线径大于16mm2,长度小于30米)到地桩或地网,部件连接(或焊接)点是否良好(锈蚀)等。
1. DCS cabinet shall adopt single point grounding method to check whether there are places that may lead to multi-point grounding, such as the contact between the cabinet and channel steel, whether the grounding point is a single down lead (wire diameter greater than 16mm2, length less than 30 meters) to the ground pile or grid, and whether the connection (or welding) points of components are good (corroded), etc.
2、检查DCS接地点与电气地或避雷针引下线接地是否共用,距离是否符合要求,一般情况要求DCS接地与电气地距离15米以上,与避雷针接地点15米以上。
2. Check whether the DCS grounding point is shared with the electrical ground or the lightning rod down lead grounding, and whether the distance meets the requirements. Generally, the distance between DCs grounding and electrical ground is more than 15 meters, and the distance between DCs grounding and lightning rod grounding point is more than 15 meters.
3、测量DCS系统接地电阻是否小于4欧姆。接地电阻的大小与很多因素相关,如接触良好,土壤湿度,导电率等,测量接地电阻可选用的仪器有摇表、钳形表等。
3. Measure whether the grounding resistance of DCS system is less than 4 ohms. The size of the grounding resistance is related to many factors, such as good contact, soil humidity, conductivity, etc. the instruments that can be used to measure the grounding resistance are megger, pincer meter, etc.
此外如果维护不注意,静电可能对DCS卡件或通讯带来不小影响,DCS维护过程中特别是在触碰硬件卡件或通讯部件时应采取如下措施做好防静电。更多相关事项就来网站http://www.sdjkyqyb.com咨询了解。
In addition, if maintenance is not careful, static electricity may have a great impact on DCS cards or communication. During DCS maintenance, especially when touching hardware cards or communication components, the following measures should be taken to prevent static electricity. Come to the website for more related matters http://www.sdjkyqyb.com Consult and understand.